N2XH FE180

Place of use

They are used at places where a lot of people can be found such as subways, tunnels, shopping centers, hospitals, airports, hotels, residential buildings, industrial facilities etc. This type of cables is halogen-free, has flame-retarder and low smoke density. These cables are used at the places where safety precautions against fire is obligatory.

Structure

Inner Conductor

Electrolytic Solid Annealed Copper Wire, Class 1 or Class 2
EN 60228, IEC 60228, VDE 0295

Insulation

Mica Tape + Cross-Linked HFFR Compound,
VDE 0293, HD 308 S2

Stranding

Pairs in Layers

İnner Sheath

HFFR Compound EN 50290-2-27

Outer Sheath

HFFR Compound EN 50290-2-27, RAL 2003 Orange

  

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C

Technical Info


CONDUCTOR
RESISTANCE

INSULATION
RESISTANCE

CURRENT CARRYING
CAPACITY

OPERATING
VOLTAGE

TEST
VOLTAGE

BENDING
RADIUS

TEMPERATURE
RANGE

 
 

mm²

Ω/km

MΩxKm

mm²

A

0,6/1 kV

2000V

15XD

-30ºC +90ºC

 

1.50

12.10

≥ 100

1.50

20

 

2.50

7.41

2.50

25

 

4.00

4.61

4.00

34

 

6.00

3.08

6.00

44

 

10.00

1.83

10.00

61

 

16.00

1.15

16.00

82

 
                           

FLAME  TEST

FLAME RETARDANT TEST

SMOKE DENSITY TEST

TEST ON CORROSIVENESS
OF COMBUSTION GASES

HALOGEN
FREE TEST

INSULATION INTEGRTY TEST
(FE 180)

 
 

IEC 60332-1-2
VDE 0482-332-1-2
EN 60332-1-2
BS EN 60332-1-2

IEC 60332-3-24
VDE 0482-332-3-24
EN 60332-3-24
EN 60332-3-24

IEC 61034-2
VDE 0482-1034-2
EN 61034-2
BS EN 61034-2

IEC 60754-2
VDE 0482-267-2-3
EN 50267-2-3
BS EN 50267-2-3

IEC 60754-1
VDE 0482-267-2-1
EN 50267-2-1
BS EN 50267-2-1

IEC 60331-23  VDE 472-814

 
 
 
                         

 

 

Catalog Info